J18500 pages
A.M.I.
J1850
INDICATOR DISPLAY PANEL WITH LEDS
Indicator display panel
with selectable inputs
rrant
y
2 rs
a
y
ye
DIN 96 x 96 format
wa
wa
www.ami-control.com
NO/NC selection
Fixed of blinking display
TRANSFER relay per way
rrant
Connector C
Connector A
Connector D
Voltage
presence
LED
«LEDs Test»
button
«Auxiliary»
button
Connector E
USE :
MAIN DIAGRAM :
- Allows local indicator display (for example in «Substation» ) of different type (Run / Stop / Alert) when the
reset and the acoustic alarm are not needed.
- $OORZ EHWWHU LGHQWL¿FDWLRQ RI DODUPV EOLQNLQJ /('
- Accepts inputs in NO/NC contact (to avoid relaying).
- Allows informations clustering for processing supervisor.
- Indicator displays with various colours :
Green, Yellow, Red, Blue
(easily unpluggable LEDs).
For each way :
- Selection of direction of input contact (NO = Normally
Open, NC = Normally Closed).
- 6HOHFWLRQ RI W\SH RI GLVSOD\ %OLQNLQJ RU ¿[HG
- Relays with 1RT contact for remote transfer of each way
separately (depending on chosen model).
+
NO/NC
Flash/Fixed
SEx
SCLx
1-8A
8 inputs
«Contact»
Lx
Rx
COM
xC
xD
xE
«LEDs Test»
external
button
«LEDs Test»
button
Transfer
relay
1B
4B
«Auxiliary»
button
5B
For the unit :
- 8 unpluggable LEDs for easy colour change.
- «LEDs Test» button on front + input for external button.
- Auxiliary button on front brought out to terminals.
- One green LED for supply voltage presence.
- 8QSOXJJDEOH WHUPLQDOV EORFN VFUHZ
2B
Input
Flash
Fixed
LEDx
3B
NO
NC
SCLx
–/
C
O
SEx
+/
AC/DC
power supply
1
0
Transfer relay
OPERATION :
SPECIFICATIONS :
- If way is selected with SEx at NC, the input contact being
closed, the light is out and the transfer relay is activated.
:KHQ WKH LQSXW FRQWDFW RSHQV /(' OLJKWV XS RU EOLQNHV
following its SCLx selection, the transfer relay drops (relay
is at safety positive. In «light out» condition with the panel
live, the contact is closed on terminals xD and xE).
- If way is selected at NO with the input contact open, the
light is out and the transfer relay is de-activated. When the
LQSXW FRQWDFW FORVHV WKH /(' OLJKWV XS RU EOLQNHV IROORZLQJ
its selection, the transfer relay is activated (in «light out»
condition with the panel live, the contact is closed on
terminals xC and xE).
Power supply voltage
24 to 48Vac/dc +/-30%
Consumption
20mA per LED + 7mA per relay
Temperature
-20°C / +60°C
Humidity
90% noncondensing
Transfer relay
1RT 6A/12Vdc - 0.15A/240Vac
Aux. push button
6A/12Vdc - 0.2A/250Vac
Weight
250g
Dimensions
96 x 96 x 67 mm
Protection without cover
24
IP52
Protection with cover
IP54
J1850-EN003-28-02-2012
LED Indicator
Display
Connector B